Panel AC Heat Load Calculator
Calculate the required cooling capacity for electrical enclosures based on physical and environmental factors
Input Parameters
mm
mm
Watts
°C
Default: 1.2
Results
Fill in the form and calculate to see results
Calculation Methodology
K-Factor by Material
Painted Steel
5.5 W/m²·°C
Stainless Steel
3.7 W/m²·°C
Aluminium
12.0 W/m²·°C
Fibreglass
3.5 W/m²·°C
Formula
Total Heat Load = (Surface Heat Transfer + Internal Heat Load) × Altitude Correction × Safety Factor
Surface Heat Transfer: k-factor × Surface Area × Temperature Difference
Internal Heat Load: 100% of equipment power (W)
Altitude Correction: Factor increases with altitude (1.0 to 1.25)
Safety Factor: Recommended 1.2 (20% margin)